beautypg.com

2 common commands, Figure 3.3 – hart diagnostics data, Table 3.10 common commands – Flowserve MX HART Field Unit User Manual

Page 29

background image

29

MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14

flowserve.com

Figure 3.3 – HART Diagnostics Data

3.5.2 Common Commands

Table 3.10 Common Commands

Command

Request Data Bytes

Response Data Bytes

No.

Description

Byte

Format

Description

Byte

Format

Description

33

Read Device

Variables

0

1

2

3

Unsigned-8

Unsigned-8

Unsigned-8

Unsigned-8

Slot 0: Device Variable Code

Slot 1: Device Variable Code

Slot 2: Device Variable Code

Slot 4: Device Variable Code

0

1

2-5

6

7

8-11

12

13

14-17

18

19

20-23

Unsigned-8

Enum

Float

Unsigned-8

Enum

Float

Unsigned-8

Enum

Float

Unsigned-8

Enum

Float

Slot 0: Device Variable Code

Slot 0: Units Code

Slot 0: Device Variable Value

Slot 1: Device Variable Code

Slot 1: Units Code

Slot 1: Device Variable Value

Slot 2: Device Variable Code

Slot 2: Units Code

Slot 2: Device Variable Value

Slot 3: Device Variable Code

Slot 3: Units Code

Slot 3: Device Variable Value

35

Write Primary

Variable Range

Values

5

0

1-4

5-8

Unsigned-8

Float

Float

Upper and Lower Range Values Units Code

Upper Range Value

Lower Range Value

0-3

4-7

Float

Float

Primary Variable Loop Current (mA)

Primary Variable % Of Range

36

Set Primary

Variable Upper

Range Value

6

37

Set Primary

Variable Lower

Range Value

7

40

Enter/Exit Fixed

Current Mode

0-3

Float

Fixed Current Level (units of milliamperes)

0-3

Float

Fixed Current Level (units of milliamperes)

41

Perform Self

Test

8

42

Perform Device

Reset

9

45

Trim Loop

Current Zero

10

0-3

Float

Externally Measured Loop Current Level

(units of milliamperes)

0-3

Float

Actual Measured Loop Current Level (units of

milliamperes)

11

This manual is related to the following products: