Software
3.1 HART Protocol
The system uses the HART protocol to communicate over the HART network with other HART devices. The HART
protocol is a master/slave communication service for process control devices. HART digital signaling is an extension of
conventional analog signaling allowing the network signal to ride on the 4-20 mADC analog process signal. It uses
1200 bps binary phase-continuous Frequency-Shift-Keying (FSK), where a high frequency current is superimposed on
a low-frequency (typically 4-20 mADC) analog current.
3.2 HART Parameters
Table 3.1 – HART Parameters
Parameter
Value
HART Version
7.3
Expanded Device Type = Manufactuer ID + Device Type
0x3008
Physical Layer Supported
FSK
Physical Device Catagory
Actuator
Maximum Number of Burst Messages
3
Maximum Number of Event Messages
1
Size of the Event Queue
6
Maximum Number of Trends
2
Size of the Trend Buffer
12
Default Number of Preambles
1
5
3.2.1 Analog Input Ratings
Table 3.2 – Analog Input Ratings
Maximum current
2
30.0 mA
Maximum voltage
50 V
Current over-range
(Primary Variable Out of Limits)
Analog Input > 21 mA
Analog Input < 3 mA
(HART communication may fail, if Analog Input <2 mA.)
Multi-drop current draw
Approximately 2 mA
1. Field Device must have minimum 5 preambles, and maximum 20 preambles.
2. The analog input is automatically bypassed, if the maximum loop current is reached. The field device will continue to check the circuit for overload on a periodic basis,
and will restore the connection if the overload clears.