Flowserve MX HART Field Unit User Manual
Page 30
![background image](https://www.manualsdir.com/files/784850/content/doc030.png)
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
30
Command
Request Data Bytes
Response Data Bytes
No.
Description
Byte
Format
Description
Byte
Format
Description
46
Trim Loop
Current Gain
12
0-3
Float
Externally Measured Loop Current Level
(units of milliamperes)
0-3
Float
Actual Measured Loop Current Level (units of
milliamperes)
13
49
Write Primary
Variable
Transducer
Serial Number
14
0-2
Unsigned-24
Primary Variable Transducer Serial Number
0-2
Unsigned-24
Primary Variable Transducer Serial Number
50
Read Dynamic
Variable
Assignments
15
0
1
2
3
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Device Variable Assigned to the Primary Variable
Device Variable Assigned to the Secondary Variable
Device Variable Assigned to the Tertiary Variable
Device Variable Assigned to the Quaternary Variable
51
Write Dynamic
Variable
Assignments
0
1
2
3
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Device Variable Assigned to the Primary Variable
Device Variable Assigned to the Secondary Variable
Device Variable Assigned to the Tertiary Variable
Device Variable Assigned to the Quaternary
Variable
0
1
2
3
Unsigned-8
Unsigned-8
Unsigned-8
Unsigned-8
Device Variable Assigned to the Primary Variable
Device Variable Assigned to the Secondary Variable
Device Variable Assigned to the Tertiary Variable
Device Variable Assigned to the Quaternary Variable
53
Write Device
Variable Units
16
0
1
Unsigned-8
Enum
Device Variable Code
Device Variable Units Code
0
1
Unsigned-8
Enum
Device Variable Code
Device Variable Units Cod
54
Read Device
Variable
Information
0
Unsigned-8
Device Variable Code
0
1-3
4
5-8
9-12
13-16
17-20
21
22
23-26
Unsigned-8
Unsigned-24
Enum
Float
Float
Float
Float
Enum
Enum
Time
Device Variable Code
Device Variable Transducer Serial Number
Device Variable Limits/Minimum Span Units
Code
Device Variable Upper Transducer Limit
Device Variable Lower Transducer Limit
Device Variable Damping Value
Device Variable Minimum Span
Device Variable Classification
Device Variable Family
Update Time Period
17
56
Write Device
Variable
Transducer
Serial No.
0
1-3
Unsigned-8
Unsigned-24
Device Variable Code
Device Variable Transducer Serial Number
0
1-3
Unsigned-8
Unsigned-24
Device Variable Code
Device Variable Transducer Serial Number
59
Write Number
of Response
Preambles
18
0
Unsigned-8
Number of preambles
0
Unsigned-8
Number of preambles
60
Read Analog
Channel and
Percent of
Range
0
Unsigned-8
Analog Channel Number Code
0
1
2-5
6-9
Unsigned-8
Enum
Float
Float
Analog Channel Number Code
19
Analog Channel Units Code = 39 (mA)
Analog Channel Level
Analog Channel Percent of Range
20
63
Read Analog
Channel
Information
0
Unsigned-8
Analog Channel Number Code
0
1
2
3
4-7
8-11
12-15
16
Unsigned-8
Enum
Enum
Enum
Float
Float
Float
Bits
Analog Channel Number Code
Analog Channel Alarm Selection Code = 250
(not used)
Analog Channel Transfer Function Code = 0
(linear)
Analog Channel Upper/Lower Range Values Units
Code = 57 (%)
Analog Channel Upper Range Value
Analog Channel Lower Range Value
Analog Channel Damping Value (seconds)
Analog Channel Flags
65
Write Analog
Channel Range
Values
21
0
1
2-5
6-9
Unsigned-8
Enum
Float
Float
Analog Channel Number Code
Analog Channel Upper/ Lower Range Values
Units Code
Analog Channel Upper Range Value
Analog Channel Lower Range Value
0
1
2-5
6-9
Unsigned-8
Enum
Float
Float
Analog Channel Number Code
Analog Channel Upper/ Lower Range Values
Units Code = 57 (%)
Analog Channel Upper Range Value
Analog Channel Lower Range Value
66
Enter/Exit Fixed
Analog Channel
Mode
0
1
2-5
Unsigned-8
Enum
Float
Analog Channel Number Code
Analog Channel Units Code
Fixed Analog Channel Level
22
0
1
2-5
Unsigned-8
Enum
Float
Analog Channel Number Code
Analog Channel Units Code = 39 (mA)
Fixed Analog Channel Level
23
67
Trim Analog
Channel Zero
0
1
2-5
Unsigned-8
Enum
Float
Analog Channel Number Code
Analog Channel Units Code
Externally Measured Analog Channel Level
0
1
2-5
Unsigned-8
Enum
Float
Analog Channel Number Code
Analog Channel Units Code = 39 (mA)
Fixed Analog Channel Level
23
68
Trim Analog
Channel Gain
0
1
2-5
Unsigned-8
Enum
Float
Analog Channel Number Code
Analog Channel Units Code
Externally Measured Analog Channel Level
0
1
2-5
Unsigned-8
Enum
Float
Analog Channel Number Code
Analog Channel Units Code = 39 (mA)
Fixed Analog Channel Level
23
71
Lock Device
0
Enum
Lock Code
0
Enum
Lock Code
76
Read Lock
Device State
0
Enum
Lock Status