Flowserve MX HART Field Unit User Manual
Page 26
MX/QX HART Field Unit FCD LMENIM2340-00 – 1/14
26
Table 3.9 MX/QX Defined Status Bits
Device-Specific Status 0 – CMD 48 Bytes 0-3 : Hardware Faults
Bit
Description
Hardware Faults – these bits will trigger More Status Available bit
0
Main board to HART board communication loss
1
Reserved
2
Valve Jam
3
Over Torque in Close direction
4
Over Torque in Open direction
5
Phase Lost
6
Motor Temperature
7
Encoder Fault
8
Main board RAM error
9
Main board FLASH error
10
Main board EEPROM error
11
Reserved
12
Knob Failure
13
Limigard Fault
14
Contactor Fault
15
Power Board
16
Digital Out Board 1 (R1-R4 & RM) board fault
17
Digital Out Board 2 (R5-R8) board fault
18
Reserved
19
Analog Board 2 Fault
20
Reserved
21
Reserved
22
Motor Controller Fault
23
Reserved
24
Oil Over Temperature (arctic units)
25
Close Torque Timer Expired
26
Open Torque Timer Expired
27
HART Board 1 Fault
28
Reserved
29
HART Board 1 memory fault
30
Reserved
31
Future
Device-Specific Status 0 – CMD 48 Bytes 4-5 : Main Board Status
Main Board Status – these bits will not trigger More Status Available bit
0
Main board Self-test Ongoing (1=ongoing, 0=finished)
1
Main board Self-test Ok (1=succeeded, 0=failed; only valid if “Self-test ongoing = 0”
2
Future
3
Future
4
Future
5
Future
6
Future
7
Future
8
Future
9
Future
10
Future
11
Future
12
Future