beautypg.com

2 scrolling status messages, 3 current alarm status, 4 status icons – Flowserve 420 IOM User Manual

Page 20: 5 adjusting the display contrast

background image

User Instructions - Logix® 420 Series Digital Positioners FCD LGENIM0106-06 12/13

flowserve.com

20


10.1.2 Scrolling Status Messages


The Scrolling Status Message provides the following
information as applicable:
Ambient Temperature

– This is the temperature inside the

positioner.
DIP Switch Override

– This indicates that the Configuration

(DIP) Switches do not reflect the actual configuration of the
positioner. This can happen if a Configuration Switch is
changed after a Quick-Cal, or if the configuration is was
changed from the DTM. Performing a Quick-Cal will reset
the configuration to what the Configuration Switches show,
which may not be desirable. Ensure the Configuration
Switches are set properly before performing a Quick-Cal.

10.1.3 Current Alarm Status


The Current Alarm Status area shows the highest priority
alarm, warning, alert or status indication. This matches the
code indicated by the flashing LEDs.

10.1.4 Status Icons


Status icons continuously show the state of the features and
modes.

Table 12: Status Icons

Icon Location

Icon

Icon Meaning

Command

Source

Analog command mode

Digital command mode

Out of service

Pressure

Control

Pressure control locked

(blank)

Pressure control not locked

HART

Communicatio

ns

HART communication currently in
progress

Burst mode in progress

(blank)

No HART communication currently
in progress



Command Source Icons

– The positioner is in Analog

Command mode if it is using the 4-20 mA signal to control
the location of the valve. In Digital Command mode, the
positioner ignores the 4-20 command and responds to the
position command given through HART. In Out Of Service
mode, the positioner is performing a calibration, signature,
partial stroke test or is in a factory reset state.


Pressure Control

– When the position of the valve gets very

close to the commanded position, the positioning algorithm
will change to pressure control. This means the pressures
will be held constant (locked), improving the stability of the
valve position. The point at which the pressure control is
locked depends on the Valve Stability switch on the
positioner. When the switch is set to “Lo Friction”, the locking
point is self-adjusting to optimize accuracy. When the switch
is set to “Hi Friction” and the deviation is smaller than +/-
1.0%, the

pressure “locks”. This value can be adjusted using

the Display Menu or DTM. See section 10.3.7 Configuration
(Pressure Control

)

.


HART Communications Icons

– When the positioner is

sending or receiving data via the HART communication
protocol, the icon will be displayed. During burst mode, a
pulsating heart icon will be displayed.

10.1.5 Adjusting the Display Contrast


To adjust the display contrast, hold the

◄ Back button for 3

seconds. Use the

▲Up and ▼ Down buttons to adjust the

contrast. Use the

►ACCEPT/QUICK-CAL to accept the

settings.