User Instructions - Logix® 420 Series Digital Positioners FCD LGENIM0106-06 12/13

flowserve.com

18


9

POSITIONER FUNCTIONS (No
Display Required)


The following features can be performed using the local
interface. No display is required for these features.
Additional features are offered with the use of a display,
Handheld or DTM.

NOTE: In order to prevent unintentional adjustments of the
configuration, tuning, or control of the valve, the Tamper Lock
feature may be used. This is set in the DTM and disables the
buttons and menus except for the ability to view the status of
the positioner. When locked, the positioner may be
temporarily unlocked by entering a PIN. (An LCD is required
to enter the PIN.) Or, the positioner can be unlocked from
the DTM.

9.1 Live Manual Tuning (Adjusting the

Gain)


Use the Selectable GAIN Switch to adjust the gain at any
time during operation. This adjustment takes effect
immediately.

For faster response select settings above “E”

(F-J)

. For more stable response, select settings below “E”

(B-D). See Figure 10: Selectable GAIN Switch on page 16.


9.2 Local Control Of Valve Position


To manually adjust the position of the valve regardless of the
input command (analog or digital), press and hold the

▲Up,

▼Down and ◄ BACK buttons for about 3 seconds. The
▲Up, ▼down buttons can then be used to position the valve.
While in this mode the LED‘s will flash a GRRY (green-red-
red-yellow) sequence. To exit the local control mode and
return

to

normal

operation, briefly press the ►

ACCEPT/QUICK-CAL button.

CAUTION: When operating using local control of the

valve, the valve will not respond to external commands.
Notify proper personnel that the valve will not respond to
remote command changes, and make sure the valve is
properly isolated.















9.3 Command Source Reset


Performing a command source reset will reset the command
source to analog if it has been inadvertently left in digital
mode. This is done by holding down both the

▲Up and

▼Down

buttons,

then

briefly

pressing

the

►ACCCEPT/QUICK-CAL button.


9.4 Factory Reset


To perfor

m a factory reset, hold ► ACCEPT/QUICK-CAL

button while applying power. All of the internal variables
including calibration will be reset to factory defaults. The
positioner must be re-calibrated after a factory reset. Tag
names and other user configured limits, alarm settings, and
valve information will also be lost and need to be restored. A
factory reset will always reset the command source to analog
4-20 mA.

CAUTION: Performing a factory reset may result in the

inability to operate the valve until reconfigured properly.
Notify proper personnel that the valve may stroke, and make
sure the valve is properly isolated.