beautypg.com

Specifications, Maintenance, Calibration – Fieldpiece SMAN2 - 3-Port Digital Manifold User Manual

Page 2: Limited warranty, Obtaining service, Pressure, Microns for vacuum (sman3 only), Temperature, Refrigerants, Battery replacement

background image

11

16

12

17

13

18

14

19

15

20

What is Superheat and Subcooling?

Why Do I Need to Measure It?

Superheat is the difference between the

actual temperature of the refrigerant (gas) as

it leaves the evaporator and the boiling point

of the refrigerant. After boiling, the refrigerant

continues to heat up. The number of degrees it

“heats up” after boiling is called the superheat.

Under worst case conditions (low load for fixed

orifice systems), the refrigerant in the evaporator

boils off near the end of the evaporator coil. To

make sure liquid doesn’t enter the compressor

under the worst case condition (low load),

the refrigerator or A/C manufacturers publish

charts indicating what the superheat should be

at a given indoor wet bulb measurement and

outdoor air temperature.

Measuring superheat is your best indication

on a fixed orifice system of the proper

refrigerant charge and operating conditions.

If everything else is working properly and the

actual superheat is too high, add refrigerant. If

it’s too low, evacuate refrigerant.

Subcooling is the difference between the

boiling point of the refrigerant in the condenser

and the actual temperature of the refrigerant

as it leaves the condenser. The degrees that the

refrigerant “cools down” below the boiling point

is the subcooling. Under worst case scenario

(low load for TXV) the subcooling will continue

to rise. If the subcooling rises too high, liquid

may be backed into the compressor causing

damage and catastrophic failure. See www.

fieldpiece.com for more technical articles.

Location of Subcooling Test

Location of Superheat Test

Specifications

Display size: 5 inches (diagonal)

Backlight: Blue (On for 1 minute unless turned off manually)

Battery: 6 x AA (Battery life below based on alkaline type)

Battery life (SMAN2): Approx. 500 hours (without backlight)

Battery life (SMAN3): Approx. 135 hours (without backlight)

Low battery indication:

is displayed when the battery

voltage drops below the operating level

Auto Shut off: 30 minutes of inactivity when APO is activated

Operating environment: 32°F to 122°F (0°C to 50°C) at <75%

relative humidity

Storage temperature: -4°F to 140°F (-20°C to 60°C), 0 to 80% RH

(with battery removed)

Temperature coefficient: 0.1 x (specified accuracy) per °C (0°C to

18°C, 28°C to 50°C), per 0.6°F (32°F to 64°F, 82°F to 122°F)

Over range: "OL" or "-OL" is displayed

Weight: 3.05 lbs (1.38 kg)

Pressure

Connector Type: Standard 1/4 NPT male flare fitting

Range: 29” HgV to 580 Psig (English), 74 cmHgV to 0 to 4000KPa

(Metric)

Resolution: 0.1 psi/inHg; 1 kPa/cmHg

Accuracy: 29” HgV to 0” HgV: ±0.2” HgV

74 cmHgV to 0 cmHgV: ±1 cmHgV

0 to 200 Psig: ±1 Psi; 0 to 1378 KPa: ±7 KPa; 0 to 1.378MPa:

±0.007MPa; 0 to 13.78 bar ±0.07 bar

200 to 580 Psig: ±0.3%+1 Psi; 1378 to 4000KPa: ±0.3%+7 Kpa;

1.378 to 4.000MPa: ±0.3%+0.007MPa; 13.78 to 40.00bar:

±0.3%+0.07bar

Maximum overload pressure: 800 psig

Units: Psig, kPa, MPa, bar, inHg, and cmHg

Microns for Vacuum (SMAN3 only)

Connector Type: Standard 1/4 NPT male flare fitting

Range: 50 to 9999 microns of mercury

Resolution: 1 micron (50 to 2000 microns), 250 microns (2001 to

5000 microns), 500 microns (5001 to 8000 microns), 1000 microns

(8001 to 9999 microns)

Accuracy: ±10% or ±10 microns, whichever is greater (50 to 1000

microns)

Maximum Overload pressure: 500 psig

Units: Microns of mercury

Temperature

Sensor type: K-Type thermocouple

Range: -95°F to 999.9°F (-70°C to 537.0°C)

Resolution: 0.1°F/°C

Accuracy: ±(1.0°F) -95°F to 199.9°F; ±(0.5°C) -70°C to 93°C

±(2.0°F) 200°F to 999.9°F; ±(1.0°C) 93°C to 537.0°C

Note: All accuracies are after a field calibration.

Refrigerants

The P-T charts of the following refrigerants come pre-programmed

into your SMAN. In your SMAN the refrigerants are listed in order of

most commonly used. Here, they are listed in numerical order for easy

reference.

R11, R113, R114, R12, R123, R1234YF, R124, R125, R13, R134A, R22,

R23, R401A(MP39), R401B, R402A, R402B, R404A, R406A, R407A,

R407C, R407F, R408A, R409A, R410A, R414B (Hotshot), R416A, R417A,

R417C (HOT SHOT 2), R420A, R421A, R421B, R422A, R422B(NU22B),

R422C(Oneshot), R422D, R424A, R427A, R434A(RS-45), R438A(MO99),
R500, R502, R503, R507A, R508B (Suva95)

Maintenance

Clean the exterior with a dry cloth. Do not

use liquid.

Battery Replacement

The battery must be replaced when the

battery life indicator

is empty. Turn your

SMAN off and replace with 6 AA batteries.

Cleaning the Sensors (SMAN3)

Over time, the vacuum sensor of the SMAN3

may become contaminated with dirt, oil, and

other contaminents introduced from pulling

vacuums.

1 Never use an object such as a cotton swab to clean the sensor,

you may cause damage to the sensor.

2 Open all knobs/valves, and cap all the ports except for the center

port.

3 Drop enough Isopropyl (rubbing) alcohol into the uncapped

port using an eye dropper or funnel so that it can flush out

contaminents.

4 Cap central port and gently shake your SMAN upside down to

clean sensor.

5 Turn right side up. Open a port to pour out the rubbing alcohol

and open all ports to allow sensors to dry out; usually an hour or

so.

Calibration

Temperature

To calibrate your SMAN temperature

thermocouples, adjust the pot on the front of

the meter labeled T1 Cal or T2 Cal. The best way

to calibrate is to match to a known temperature.

Ice water is very close to 32°F and is readily

available. Accuracies of one degree or better

are easily obtained.

1 Stabilize a large cup of ice water by stirring. Pure, distilled water

will be the most accurate.

2 Press the circular button until your SMAN enters Direct

Temperature (T1 T2) mode.

3 Immerse the temp probe in ice water from T1 and adjust the

T1 Cal pot with a flathead screwdriver and let it stabilize, keep

stirring.

4 Repeat Step 3 for temp probe in T2.

Pressure Zeroing

To calibrate your SMAN pressure sensors to

atmospheric pressure, ensure that your SMAN

is disconnected from any pressure source and

at equilibrium with the ambient pressure.

1 SMAN must be in Superheat/Subcooling, Saturation, or T1 T2

Direct mode.

2 Press the CAL Atmospheric Pressure button and your SMAN will

set the zero point of pressure to the ambient pressure.

Advanced Pressure Calibration

Your SMAN has the ability to perform a linear

adjustment of the pressure sensors based on

refrigerant type, temperature, and pressure.

Calibration setup: For best results, perform both the Temperature

and Pressure Zeroing procedures. See Calibration section for

details. This will ensure pressure readings are zeroed and

thermocouple is properly calibrated to the T1 port of the SMAN.

Calibration to T2 port is not necessary for this calibration.

The refrigerant cylinder should be stored in a stable ambient

environment for at least 24 hours before calibration.

1 Press circular button until your SMAN enters T1 T2 Direct mode.

2 Plug in a K-type thermocouple into T1. (A bead type

thermocouple, like the ATB1, is recommended.)

3 Connect the SMAN to a refrigerant cylinder of a known, single

refrigerant using an EPA approved service hose. Be sure to open

both HIGH and LOW side valves on your manifold and cap the

unused ports. (If caps are not available you can connect both ends

of a refrigerant hose to the two unused caps. Note you will lose

some refrigerant into the hose using this method.)

4 Press the REFRIGERANT button to match the refrigerant of the

cylinder you are using.

5 Attach bead-type thermocouple to the side of the cylinder using

tape. It is recommended to attach in the middle of the cylinder.

Important: Let the temperature of the thermocouple stabilize to

the refrigerant temperature for 1 to 2 minutes or until stable.

6 Open the refrigerant cylinder. The pressure inside cylinder should

now be displayed on both HIGH and LOW side pressure sensors.

7 Press the CAL Test Pressure button. If successful, "Good" will

display for 3 seconds. If failed, "Err" will display for same time.

Your SMAN checks with its built-in P-T charts to compare the

temperature of the refrigerant in the tank to the vapor saturation

temperature based on the refrigerant you selected. If the measured

pressures on your SMAN are within ±3psi of the P-T chart pressure

corresponding to the vapor saturation temperature, the SMAN will

adjust the pressure sensor linearity to match the P-T chart.

Possible causes of failed "Err" pressure calibration:

1. Refrigerant tank was not stored in stable ambient conditions for at

least 24 hours.

2. Thermocouple attached to refrigerant tank was not properly

calibrated to T1 port of SMAN.

3. Thermocouple was plugged into wrong port T2 instead of T1.

4. Incorrect refrigerant was selected on the SMAN.

Limited Warranty

This meter is warranted against defects in

material or workmanship for one year from

date of purchase. Fieldpiece will replace or

repair the defective unit, at its option, subject

to verification of the defect.

This warranty does not apply to defects

resulting from abuse, neglect, accident,

unauthorized repair, alteration, or unreasonable

use of the instrument.

Any implied warranties arising from the sale of

a Fieldpiece product, including but not limited

to implied warranties of merchantability and

fitness for a particular purpose, are limited to

the above. Fieldpiece shall not be liable for loss

of use of the instrument or other incidental or

consequential damages, expenses, or economic

loss, or for any claim of such damage, expenses,

or economic loss.

State laws vary. The above limitations or

exclusions may not apply to you.

Obtaining Service

Call Fieldpiece Instruments for current costs

on our fixed price warranty service. Send

check or money order for the amount quoted.

Send your digital manifold, freight prepaid, to

Fieldpiece Instruments. Send proof of date and

location of purchase for in-warranty service.

The meter will be repaired or replaced, at the

option of Fieldpiece, and returned via least cost

transportation.

For international customers, warranty for

products purchased outside of the U.S. should

be handled through local distributors.

www.fieldpiece.com

© Fieldpiece Instruments, Inc 2013; v32

High Side

Low Side

TXV

Compressor

Direction of

Refrigerant

Flow

Condenser

Evaporator

!

WARNINGS

DO NOT APPLY MORE THAN 800 PSI TO ANY PORT ON THE MANIFOLD.

FOLLOW ALL EQUIPMENT MANUFACTURER'S TESTING PROCEDURES

ABOVE THOSE IN THIS MANUAL IN REGARDS TO PROPERLY

SERVICING THEIR EQUIPMENT.