Figure 35: can temp sensor wiring – Daktronics AF-3180-64-R,A User Manual
Page 36

3.9 Optional Temperature Sensor Electrical Installation
Reference Drawing:
Schem, Sig Wiring, W/Quick Connect PCB ................ Drawing B-177662
After mounting the optional temperature sensor as described in Section 2.6 follow
these steps to complete the electrical installation.
Using the Quick Connect and 10 foot cable
1. The temperature sensor is provided with 10 feet
of weather resistant cable. The cable does not
need to be in conduit.
2. Route the cable to the display and connect the
Quick Connect to the Temp Sensor input on the
back of the first display (J31). Be sure to secure
any excess cable from be pulled loose in the wind.
Using the Quick Connect and less then the 10
foot cable
1. Disconnect the CAN temp sensor cable from the temperature sensor
terminal block in the CAN temp sensor housing. (0A-1151-0005)
2. Cut the cable to desired length and reattach to the temperature sensor
terminal block in the CAN temp sensor housing as follows:
Wire Color
Temp Sensor
Terminal Block (TB1)
Red
+5V CAN (Pin 1)
Green
CANH (Pin 2)
White
CANL (Pin 3)
Black
GND (Pin 4)
*Note: Do not terminate shield at this point.
Figure 35: CAN Temp Sensor Wiring
Electrical Installation
3-16