Figure 21: Installation with Ground and Neutral Conductor Provided

Installation with Only a Neutral Conductor Provided

Installations where no grounding conductor is provided must comply with article
250-32 of the National Electrical Code. If the installation in question meets all of the
requirements of article 250-32, the following guidelines must be observed:

• Connect the grounding electrode cable at the local disconnect, never at the

display panel board.

• A disconnect that opens all of the ungrounded phase conductors should be

used.

• The neutral and the ground conductors should be bonded in the display

panel board.

Refer to Figure 21 below for installation details.

Figure 22: Installation with only Neutral Conductor Provided

Electrical Installation