Specifications

4.1

Electrical

Input Voltage ..............................10-36 VDC ................................. 8-24 VAC
Input Power (max)......................10 W........................................... 10 VA
Input Frequency .........................N/A ............................................. 47-63 Hz
Fault Relay Contacts..................24 V, 500 mA (max)

4.2

Environmental

Operating Temperature..................0°C to +60°C
Storage Temperature ................ –40°C to +85°C
Humidity ....................................... 10% to 95% ........................ Non-Condensing

4.3

Functional

Operating Systems for

EISC Configurator : .................Windows 98/ME/2K/XP

Aging (typical) ............................300 seconds

Connectors :

Type

Function

Attached Wiring

RJ-45,

shielded.......................Fieldbus ........................ Category

5

DB-9........................................Console......................... Null-Modem

Cable

Screw,

2-terminal....................Fault

Relay.................... 16-22 AWG, solid

Screw,

4-terminal....................Power............................ 16-22 AWG, solid

LED Indicators :

Function

Color

Power............................ Green
Link/Activity ................... Green/Yellow
Status............................ Green/Yellow

Flow Control :

Half-Duplex Full-Duplex

Backpressure.................................... PAUSE (IEEE 802.3x)

Transceiver Parameters :

Twisted-Pair

Fiber

Signaling .......................................... 10BASE-T/100BASE-TX .................. 100BASE-FX, 1300 nm
Data Rates ....................................... 10/100 Mbps..................................... 100 Mbps
Port Count ........................................ 16 or 10 ............................................ 0 or 2
Connectors....................................... RJ-45, shielded................................. SC or ST
Segment length (max)...................... 100 m................................................ 2 km, multimode

15 km, single mode