Returning VFD to factory default settings:
Sometimes the easiest way to ensure that the VFD has the correct operating parameters is to
return the configuration parameters to factory default and re-enter the few parameters changed
for use with the TG-25 and the TG-50s. There are currently over 50 adjustable parameters
available with this VFD of which 11 need to be changed from factory default
To reset the VFD to operate on the TGs, reset the parameters to the factory default as shown
below and re-enter and/or verify the parameters in the programming section above.
MENU PARAMETER
SECONDARY
PARAMETER
FUNCTION SETTING
FUn FCS
Reset
configuration to
factory default
Lnl (Must hold ENT
key for 2 sec)
ONLY USE THIS
PARAMETER TO
RETURN VFD TO
FACTOR DEFAULT
CONFIGURATION.
IF
Note The drive must be stopped to modify this parameter.
Remove jumper wire from terminal 15 to
stop drive
FAULTS – CAUSES – REMEDIES
Clearing the fault:
Cut the power supply to the drive in the event of a non-resettable fault.
Wait for the display to go off completely.
Find the cause of the fault in order to correct it.
Restore the power supply – this clears the fault if it has disappeared.
Drive does not start, no fault displayed:
Check that the run command input has been jumpered (Jumper is required between terminals
LI1 and +15V).
When the drive is switched on, or at a manual fault reset, or after a stop command, the motor
can only be supplied with power once the ”forward” commands have been reset. Otherwise, the
drive will display “rdy” or “nSt” but will not start.