3.5. Signal state control functions

The General Control Block is used for controlling the refresh of a single signal state. It will be
refreshed and, through the ready mask, reported ready by setting the corresponding bit in the
call mask. After it was reported ready the bit must be cleared from the call mask, only then
communications can be started again. The refresh of signal states can be interrupted. When
there is a refresh in process and if there is a refresh of a higher priority called in the call mask,
the process is interrupted.
In case errors are detected in the fo-ring in a normal system run, the corresponding bits in the
error mask are set.

Address

(hex)

Contents

Comment

0FFF

call mask

0FFE

IRQ-output

0FFD

ready mask

0FFC

IRQ-input

0FFB

write protection

The value 02h removes the write

protection

0FFA

error mask

0FF9

-

reserved for later use

...

-

- " -

0FF1

VMEbus Interrupt

Vector

Vector numbers 0h-FFh for D08
interrupter

0FF0

VMEbus Interrupt

Level

2h = IRQ1,4=IRQ2 80h=IRQ7

mask register