Test and analysis functions – BECKHOFF C1300 User Manual
Page 17
C1300 VME to II/O Interface Unit
Beckhoff II/O-System
Date : 18.12.95
Version : 2.01
Page 17 of 44
3.3. Test and Analysis Functions
Function 01h : FO-RESET
This function initialzes the fo-ring.In the course of the initialization the number of
modules in the ring is detected, the module addresses are distributed and tested.
Finally the ring is tested for its (Dämpfungsreserve). A fraction that could occur in
the cable is detected and localized.
channel
length
function
argument 0 argument 1 argument 2
comment
call
02
01
response
05
01
00
00
nn
Function worked properly
(nn modules in the fo-ring)
05
01
01
01
00
Maximum of transmission
repetitions exceeded
05
01
01
02
00
No addressing possible
05
01
0a
01
nn
Fraction before module nn,
before receiver line in of
module C1300
05
01
0a
01
ff
Fraction cannot be localized
( fraction before
line in of receiver )
05
01
07
01
nn
Test addresses :
Address error ( modul nn)
05
01
05
02
00
Absorbtion test :
error at High-Intensity
05
01
05
03
nn
Absorbtion test :
Error switching low intensity
( modul nn)
05
01
05
04
nn
Absorbtion test :
Error at data pattern 1
( pattern 00) (module nn)
05
01
05
05
nn
Absorbtion test :
Error data pattern 2
( pattern FF) (module nn)
05
01
05
06
nn
Absorbtion test :
Error data pattern 3
( pattern AA)(module nn)
05
01
05
07
nn
Absorbtion test :
Error switching high-intensity
(module nn)
If the ring initialization is completed and no errors occured, the present number of
modules in the ring is transmitted. If an error was detected, the error type (see
table) and the modul addresses of the error detecting module are returned.