C1300 VME to II/O Interface Unit

Beckhoff II/O-System

Date : 18.12.95

Version : 2.01

Page 17 of 44

3.3. Test and Analysis Functions

Function 01h : FO-RESET

This function initialzes the fo-ring.In the course of the initialization the number of
modules in the ring is detected, the module addresses are distributed and tested.
Finally the ring is tested for its (Dämpfungsreserve). A fraction that could occur in
the cable is detected and localized.

channel

length

function

argument 0 argument 1 argument 2

comment

call

02

01

response

05

01

00

00

nn

Function worked properly
(nn modules in the fo-ring)

05

01

01

01

00

Maximum of transmission
repetitions exceeded

05

01

01

02

00

No addressing possible

05

01

0a

01

nn

Fraction before module nn,
before receiver line in of
module C1300

05

01

0a

01

ff

Fraction cannot be localized
( fraction before
line in of receiver )

05

01

07

01

nn

Test addresses :
Address error ( modul nn)

05

01

05

02

00

Absorbtion test :
error at High-Intensity

05

01

05

03

nn

Absorbtion test :
Error switching low intensity
( modul nn)

05

01

05

04

nn

Absorbtion test :
Error at data pattern 1
( pattern 00) (module nn)

05

01

05

05

nn

Absorbtion test :
Error data pattern 2
( pattern FF) (module nn)

05

01

05

06

nn

Absorbtion test :
Error data pattern 3
( pattern AA)(module nn)

05

01

05

07

nn

Absorbtion test :
Error switching high-intensity
(module nn)

If the ring initialization is completed and no errors occured, the present number of
modules in the ring is transmitted. If an error was detected, the error type (see