3. Function Description Software

3.1. About the Software

Address space (hex)

Funktion

000 - BFF

Data area
(input, output )
3 kByte

C00 - CFF

Handshake-channel 0 : VME -> C1300
(configuration, test, analysis)

D00 - DFF

Handshake-channel 1 : C1300 -> VME
(configuration, test, analysis)

E00-FF9

reserved

FFA - FFF

GCB (General Control Block)
(demand, ready und error mask)

Overview : Distribution of the port‘s workspace.

The port between VMEbus and C1300 module enables the following functions:

-

Data exchange of signal states

-

Test- und analysis functions for II/O-System

-

Configuration

-

Control of signal states

The II/O System can be configurated through the comunications channels by 4 functions. This
way the input and output lines are distributed to the addresses in the DPRAM. The
communications channels can also be used to reach nine more functions for testing and anal-
ysis.
The lower 2 Kbyte area, which is used by the C1300 module in the VME address space, is the
place for the data areas of the CDLs. The call to refresh the signal states is done by setting a
bit in the demand mask of the GCB ( General Control Block ). The ready message can be