Basler Electric BE1-25A User Manual
Page 17
Generator Speed
Adjustable between 0 to 99.9 seconds in 0.1 second increments.
Correction Pulses
Shock
In standard tests, the relay withstood 15 G in each of three mutually
perpendicular axes without structural damage or degradation of
performance.
Vibration
In standard tests the relay withstood 2 G in each of three mutually
perpendicular axes swept over the range of 10 to 500 Hz for a total of
six sweeps, 15 minutes each sweep, without structural damage or
performance degradation.
Isolation
1,500 Vac at 60 Hz for one minute in accordance with IEC 255-5 and
ANSI/IEEE C37.90-1978 (Dielectric Test).
Surge Withstand Capability
Qualified to ANSI/IEEE C37.90.1-1989, Standard Surge Withstand
Capability Tests, and to IEC 255-5, Impulse Test and Dielectric Test.
Radio Frequency Interference
Field tested using a five-watt, hand-held transceiver operating at
random frequencies centered around 144 MHZ and 440 MHZ, with
the antenna located six inches from the relay in both horizontal and
vertical planes.
Maintains proper operation when tested for interference in
accordance with IEC C37.90-1989, Trial-Use Standard Withstand
Capability of Relay Systems to Radiated Electromagnetic Interference
from Transceivers.
Patent
Patented in U.S., 1998, Patent No. 5761073.
UL Listed
UL listed per Standard 508, UL File Number E97033.
C.S.A. Certification
CSA certified per Standard CAN/C.S.A.-C22.2 Number 14.
CE Qualification
This product meets or exceeds the standards required for distribution
in the European community.
GOST-R Certification
GOST-R certified per the relevant standards of Gosstandart of
Russia.
Temperature
Operating
–40 to 70°C (–40 to 158°F)
Storage
–65 to 100°C (–85 to 212°F)
Weight
16.0 lb (7.26 kg) net for basic synchronizer (Includes the rack frame,
MCU module, and power supply module.)
9146600990 Rev S
BE1-25A General Information
1-7