beautypg.com

Instructions – Basler Electric AVC63-12 User Manual

Page 6

background image

Publication

9337200991

Revision

J

Instructions

Date

01/15

Page

6 of 10

Figure 8. Connections for Cross-Current Compensation

Table 1. Terminal Descriptions

Term #

Description

Upper Termi

na

l Strip

CH GND

Chassis ground connection

2

Auxiliary input from SCP250 and/or EL 200 (See Fig. 7)

3

4

Internal voltage adjust: connect to 7. External voltage adjust: no
connection

5

1 A current transformer (CT)

5a

5 A CT

6

CT common connection

6a

Common connection for selectable features

7

Internal voltage adjust: connect to 4. External voltage adjust:
connect to 6a

8

Connect to 6a to select 1 V/Hz underfrequency slope

9

Connect to 6a to select 3-phase sensing

Lower Term. Strip

Term #

Description

20 C-phase sensing input
22 A-phase sensing input
24 B-phase sensing input
26

1- or 3-phase power input

28 3-phase power input
30

1- or 3-phase power input

F1

Field + connection

F2 Field

– connection

The secondary winding of a sensing transformer must be grounded as closely to the
transformer as practical. When interconnecting more than one transformer, ensure that
the secondary winding of only one transformer is grounded.

GEN 1

GEN 2

5 or 5A

6

AVC

0.1

0.1

CT

CT

LOAD

CCC
ENABLE
CONTACT

5 or 5A

GEN 3

0.1

CT

P0

009-

26.

vsd

0

3

-07-

12

5 or 5A

52b

1

52

1

52

2

52b

2

52b

3

52

3

AVC

AVC

6

6

1

The secondary winding of a sensing transformer must be grounded as closely to
the transformer as practical. When interconnecting more than one transformer,
ensure that the secondary winding of only one transformer is grounded.

1

This manual is related to the following products: