Maintenance, Troubleshooting, Instructions – Basler Electric AVC63-12 User Manual

Page 10

background image

Publication

9337200991

Revision

J

Instructions

Date

01/15

Page

10 of 10

3.

Adjust the VLT ADJ control clockwise.

Observe that the lamp turns on.

4.

Adjust the VLT ADJ control until the lamp just turns off.

Table 2. Test Voltage and Frequency

Model

Input

Power

Sensing

Vac

Hz

AVC63-12A1 120

120

50/60

AVC63-12A2 120

120

400

AVC63-12B1 120

240

50/60

AVC63-12B2 120

240

400

AVC125-10A1 240

120

50/60

AVC125-10A2 240

120

400

AVC125-10B1 240

240

50/60

AVC125-10B2 240

240

400

Regulator operation is satisfactory if the above results are obtained. However, stability must be tested with the
generator and regulator in operation.

Figure 10. Test Setup

MAINTENANCE

A periodic inspection of the regulator should be made to ensure that it is clean and free from accumulations of
dust and moisture. Ensure that all connections are clean and tight.

TROUBLESHOOTING

In case of regulator failure or defective operation, simplifying the system by eliminating components such as
remote adjust potentiometers and other non-essential items can be helpful in the troubleshooting process.

F1

F2

26

30

20

22

AVC63-12 or AVC125-10

D2

59

0-33

0

3

-2

4-

06

10

ohms

Input

Power

100 W

Lamp

24

28

2

3

5

6

6a

7

8

5a

9

4

CH

GND

Sensing

Voltage

20

ohms

1

1

A wire-wound resistor with a minimum
power rating of 15 W should be used.