Mounting, Instructions – Basler Electric AVC63-12 User Manual
Page 3
![background image](https://www.manualsdir.com/files/773896/content/doc003.png)
Publication
9337200991
Revision
J
Instructions
Date
01/15
Page
3 of 10
AVC125-10
250 Vdc,
10% in approximately 10 s
360 Vdc,
10% in approximately 4 s or less
1
10
100
70
90
110
130
150
170
190
210
230
Ti
m
e
in
Se
conds
DC Output Voltage
Figure 4. AVC63-12 Overexcitation
Shutdown Characteristics
1
10
100
240
260
280
300
320
340
360
Ti
m
e
in
Se
conds
DC Output Voltage
Shutdown Region
Figure 5. AVC125-10 Overexcitation
Shutdown Characteristics
Droop/Line Drop Compensation
<10 VA adjustable from 0 to 10% of rated input current at 0.8 power factor. (LDC compensates only for voltage
drop due to line reactance and reactive components of the load current.)
Agency Approvals
UL Recognition
UL 6200, File E97035
CSA Certification
Standard CAN/CSA-C22.2 No. 14-95, File LR 23131
CE Conformity
Radiated Emissions:
EN50081-2
Conducted Emissions: EN50081-2 (EN55011, Class A)
Conducted Emissions: EN50081-2 (EN55011, Class A)
ESD Immunity:
EN50082-2 (4 kV contact, 8 kV air)
EFT Immunity:
EN50082-2 (2 kV coupling clamp)
Magnetic Immunity:
EN50082-2 (30 Arms, 50 Hz)
Safety: EN61010-1
Radiated Immunity
Electric Field:
EN61000-4-3 (10 V/m)
Conducted:
EN61000-4-6 (10 Vrms)
Type Tests
Shock
Withstands 20 G in each of 3 mutually perpendicular planes.
Vibration
Withstands 4.5 G at 18 to 2,000 Hz
Physical
Temperature
Operating:
–40 to 70
C (–40 to 158F)
Storage:
–40 to 70
C (–40 to 158F)
Max. Humidity:
95%, non-condensing
Weight:
1.1 kg (2.5 lb)
MOUNTING
Regulators are contained in an encapsulated plastic case and may be mounted in any convenient position. A
regulator may be mounted directly on a genset using UNC ¼-20 or equivalent hardware. Hardware selection
should be based on any expected shipping/transportation and operating conditions. The torque applied to the
mounting hardware should not exceed 65 in-lb (7.34 N
m). See Figure 6 for regulator dimensions.