5-4

BE1-79M Tests and Adjustments

9170100990 Rev N

STEP 16. Prepare for continuous continuity testing between terminals 17 and 18. Initial test should indi-

cate continuity if I.T.E. NO option is selected. If I.T.E. NC option is selected, all continuity

indications will be the opposite of that described for this step.

a. Press and release S6. The INST. LED should light, and there should be continuity between

terminals 17 and 18.

b. Press and release S6. In 1 second, the STATUS 1 LED should light, and there should be

continuity between terminals 17 and 18.

c. Press and release S6. In 1 second, the STATUS 2 LED should light, and there should be

continuity between terminals 17 and 18.

d. Press and release S6. In 1 second, the STATUS 3 LED should light and continuity between

terminals 17 and 18 should exist.

e. Press and release S6. The LOCKOUT LED should light.

f. Press and release S7. There should be continuity between terminals 17 and 18. If Control

Output option is F or G (I.T.E. Cold Load), terminals 17 and 18 will

NOT have continuity.

Disconnect continuity tester.

STEP 17. In 60 seconds, the RESET LED should light and the LOCKOUT LED should extinguish. Tog-

gling the front panel RESET lever should extinguish the STATUS 1, 2, 3, and INST. LEDs. If

automatic reset of STATUS LEDs is selected, the STATUS 1, 2, 3, and INST. LEDs will extin-

guish when the relay reaches RESET. Place all INSTANTANEOUS TRIP switches into the

BLOCK position.

NOTE

Step 18 applies only to units with the Reclose Failure options (i.e., - Lockout

and Reset options 2, 5, 6, or 8).


STEP 18. Disconnect the test circuit from terminal 16. Set RECLOSE FAIL thumbwheel setting to 50 (i.e.,

5.0 seconds). Press and release switch S6 (K1 latch). The INST. and OUTPUT ENERGIZE

LEDs should light. In approximately 5 seconds, the OUTPUT ENERGIZE LED should go out

and the RECLOSE FAIL and LOCKOUT LEDs should light. Check for continuity between ter-

minals 12 and 13. Press and release switch S7 (K1 reset). Wait for RESET LED to light.

Toggling the front panel RESET lever should extinguish the INST. LED. If automatic reset of

STATUS LEDs is selected on logic switch S23, the STATUS INST. LED will extinguish when

the relay reaches RESET. Reconnect the test circuit to terminal 16.

STEP 19. Set MAX. CYCLE thumbwheel setting to 020. If present, set RECLOSE FAIL thumbwheel

setting to 00. Press and release switch S6 (K1 latch). The INST. and OUTPUT ENERGIZE

LEDs should light. In approximately 20 seconds, the MAX. CYCLE and LOCKOUT LEDs

should light. Press and release switch S7 (K1 reset) and wait for RESET LED to light. Toggling

the front panel RESET lever should extinguish the INST. LED. If automatic reset of STATUS

LEDs is selected on logic switch S23, INST. LED will extinguish when the relay reaches RE-

SET. Reconnect the test circuit to terminal 16.

NOTE

Step 19 applies only to units with the Maximum Cycle options (i.e., - Lockout

and Reset options 4, 6, 7, or 8).


STEP 20. Close RI and IRB input switches.
STEP 21. Press and release S7 (K1 reset) and allow reclose time delay to expire.