BE1-79M General Information
1-5
Radio Frequency
Interference (RFI)
Maintains proper operation when tested for interference in accordance
with IECC C37.90.2-1989, Trial-Use Standard Withstand Capability of
Relay Systems to Radiated Electromagnetic Interference from
Transceivers, and 99-1188, field tested using a 5 watt, hand held
transceiver operating at random frequencies centered around 144 MHz
and 440 MHz, with the antenna located 6 inches from the relay in both
horizontal and vertical planes.
Shock
In standard tests, the relay has withstood 15g in each of three mutually
perpendicular planes without structural damage or degradation of
performance.
Vibration
In standard tests the relay has withstood 2g in each of three mutually
perpendicular planes swept over the range of 10 to 500 Hz for six
sweeps, 15 minutes each sweep, without structural damage or
degradation of performance.
Isolation
At terminals 1 through 4 and 11 through 20, the maximum voltage
applied must be no greater than 300 V because of the MOV
suppressors employed at these locations. At the remaining terminals,
2,500 Vac at 60 Hz for one minute may be applied in accordance with
IEC 255-5 and ANSI/IEEE C37.90-1989 (Dielectric Test).
Surge Withstand Capability
Oscillatory
Fast Transient
Qualified to ANSI/IEEE C37.90.1-1989 Standard Surge Withstand
Capability (SWC) Tests for Protective Relays and Relay Systems.
Qualified to ANSI/IEEE C37.90.1-1989 Standard Surge Withstand
Capability (SWC) Tests for Protective Relays and Relay Systems.
Impulse Test
Qualified to IEC 255-5.
GOST-R Certification
GOST-R certified per the relevant standards of Gosstandart of Russia.
Weight
13 lbs (5.9 kg)
Case Size
S1; Refer to Section 4, Installation.