BE1-79M General Information

1-5

Radio Frequency

Interference (RFI)

Maintains proper operation when tested for interference in accordance

with IECC C37.90.2-1989, Trial-Use Standard Withstand Capability of

Relay Systems to Radiated Electromagnetic Interference from

Transceivers, and 99-1188, field tested using a 5 watt, hand held

transceiver operating at random frequencies centered around 144 MHz

and 440 MHz, with the antenna located 6 inches from the relay in both

horizontal and vertical planes.

Shock

In standard tests, the relay has withstood 15g in each of three mutually

perpendicular planes without structural damage or degradation of

performance.

Vibration

In standard tests the relay has withstood 2g in each of three mutually

perpendicular planes swept over the range of 10 to 500 Hz for six

sweeps, 15 minutes each sweep, without structural damage or

degradation of performance.

Isolation

At terminals 1 through 4 and 11 through 20, the maximum voltage

applied must be no greater than 300 V because of the MOV

suppressors employed at these locations. At the remaining terminals,

2,500 Vac at 60 Hz for one minute may be applied in accordance with

IEC 255-5 and ANSI/IEEE C37.90-1989 (Dielectric Test).

Surge Withstand Capability
Oscillatory

Fast Transient


Qualified to ANSI/IEEE C37.90.1-1989 Standard Surge Withstand

Capability (SWC) Tests for Protective Relays and Relay Systems.
Qualified to ANSI/IEEE C37.90.1-1989 Standard Surge Withstand

Capability (SWC) Tests for Protective Relays and Relay Systems.

Impulse Test

Qualified to IEC 255-5.

GOST-R Certification

GOST-R certified per the relevant standards of Gosstandart of Russia.

Weight

13 lbs (5.9 kg)

Case Size

S1; Refer to Section 4, Installation.