Operational characteristics, Power-up, Operational characteristics -6 – Basler Electric BE1-79M User Manual
Page 30: Power-up -6, Table 3-3. wide range power supply voltage ranges, N table

3-6
BE1-79M Functional Description
9170100990 Rev N
Table 3-3. Wide Range Power Supply Voltage Ranges
Power Supply
Style Chart Identifier
Nominal Voltage
Voltage Range
Low Range
L
24 Vdc
12 to 32 Vdc ∗
Mid Range
J, K, Y
48, 125 Vdc,
120 Vac
24 to 150 Vdc,
90 to 132 Vac
High Range
Z
125, 250 Vdc,
120, 240 Vac
62 to 280 Vdc,
90 to 270 Vac
∗
14 Vdc required to start the power supply.
Relay operating power is developed by the wide range, isolated, low burden, flyback switching, solid-state
power supply. Nominal +12/–12 Vdc is delivered to the relay internal circuitry. Input (source voltage) for
the power supply is not polarity sensitive. A red LED turns
ON to indicate that the power supply is func-
tioning properly.
Operational Characteristics
Due to the microprocessor-based design of the BE1-79M Multiple Shot Reclosing Relay, many of its
operational characteristics are not apparent in the block diagram. The remaining information in this sec-
tion is focused on the software-controlled features of the relay.
Power-Up
The application of operating power results in one of four states as illustrated in Figure 3-4. Depending on
conditions and the RESET delay setting, the interval from power application to the resultant state may be
from 10 to 1000 seconds or optionally from 1 to 100 seconds. When the resultant state is reached, the
relay fail output contacts open and the RELAY FAIL LED is extinguished.