Specifications, Temperature, Specifications -4 – Basler Electric BE1-79M User Manual
Page 14: Temperature -4

1-4
BE1-79M General Information
9170100990 Rev N
Specifications
The BE1-79M Relay is available with the following features and capabilities.
Contact Sensing
Reclose Initiate
Breaker (52b)
Pilot Initiate
Instantaneous Reclose
Bypass
Drive to Lockout
The contact sensing circuits require user-supplied contacts with a
minimum rating of 0.025 A at 250 Vdc. Sensing current is supplied by
the relay in styles with isolated sensing. Styles with non-isolated
sensing require an applied sensing voltage equal to the relay dc power
supply input rating. Burden per contact for non-isolated sensing,
dependent on power supply type, is listed in Table 1-1.
Power Supply
Refer to Table 1-2.
Outputs
Output contacts are rated as follows:
120 Vac
Make, break, and carry 7 Aac continuously.
Resistive
250 Vdc
Make and carry 30 Adc for 0.2 seconds, carry 7 Adc
continuously, break 0.3 Adc.
500 Vdc
Make and carry 15 Adc for 0.2 seconds, carry 7 Adc
continuously, break 0.3 Adc.
120 Vac, 125 Vdc, 250 Vdc Break 0.3 A (L/R = 0.04)
Inductive
Timing
Reclose
Pilot (Optional)
Adjustable from 00.1 to 99.9 seconds in 0.1 second increments.
Accurate within 1% of setting or 0.05 seconds, whichever is greater.
Optionally adjustable from 1 to 999 seconds in one second increments
for the second and third reclose time delays. Accurate within 1% of
setting or 0.5 seconds, whichever is greater.
Optionally adjustable from 0.03 to 0.99 seconds in 0.01 increments.
Accurate to within ±0.01 seconds of setting. If reclose time delay option
A8 is not specified, pilot reclose time is ≤ 0.035 seconds.
Reset
Adjustable from 10 to 1,000 seconds in 10-second increments or
optionally adjustable from 1 to 100 seconds in 1 second increments. A
setting of 00 indicates a 1000 second reset time or optionally a 100
second reset time. Accurate within 1% of setting or 0.5 seconds,
whichever is greater.
Reclose Fail (Optional)
Adjustable from 0.1 to 9.9 seconds in 0.1 second increments. Accurate
within 1% of setting or 0.05 seconds, whichever is greater.
Maximum Cycle (Optional)
Adjustable from 1 to 1000 seconds in 1 second increments. Accurate
within 1% of setting or 0.5 seconds, whichever is greater.
Temperature
Operating
–40°C (–40°F) to 70°C (158°F)
Storage
–65°C (–85°F) to 100°C (212°F)