Basler Electric BE1-79M User Manual
Page 21

9170100990 Rev N
BE1-79M Human-Machine Interface
2-3
Locator
Control or Indicator
Function
N
MAX. CYCLE or PILOT TIME
Control (Optional)
With MAX. CYCLE, establishes maximum cycle limit
(maximum allowable interval from initiation of reclosing
sequence until RESET or LOCKOUT). Thumbwheel
adjustable from 1 to 1000 seconds in 1 second increments.
A setting of 000 allows a 1000-second maximum cycle.
With reclose time delay option A8 (PILOT TIME), the two
least significant digits are used for the pilot time delay for a
pilot reclose attempt. Thumbwheel adjustable from 0.03 to
0.99 seconds. A setting of .00, .01, and .02 is equivalent to
.03 setting.
O
NORMAL/TEST Switch
Provides selection of relay operating mode.
P
Logic Switch
Field selectable, 16 position switch (S23) enables
combinations of the following functions.
•
Memory save
•
Power-up to reclose
•
Recognition dropout
•
Status LED reset
Refer to Table 2-2 for switch positions and functions
enabled. To be enabled, function changes require relay
power removal and power-up after setting switch position.
CAUTION
With Power-up to Reclose enabled, relay will close the breaker during power-
up if relay was in RESET when powered down and Pilot Initiate or Reclose
Initiate is present during power-up.