beautypg.com

General, Functional description, Contact sensing – Basler Electric BE1-79M User Manual

Page 25: Section 3 • functional description -1, General -1, Functional description -1, Contact sensing -1, Table 3-1. function of sensing contacts

background image

9170100990 Rev N

BE1-79M Functional Description

3-1

SECTION 3 • FUNCTIONAL DESCRIPTION

General

The BE1-79M Multiple Shot Reclosing Relay is a microprocessor-based device, which responds to the

state of external contacts. In responding, the Relay provides automatic reclosure once the circuit breaker

has opened to de-energize the line. Refer to Section 1 for major factors to consider when establishing a

reclosing philosophy.

Functional Description

The following paragraphs describe the Relay circuit functions illustrated in Figure 3-1.

Contact Sensing

Depending on style, contact-sensing current is obtained either directly from the Multiple Shot Reclosing

Relay or from any power source with a voltage rating the same as the Relay power supply dc input vol-

tage. When the Relay provides the contact sensing current, isolated contact sensing is employed. When

another power source provides the contact sensing current, non-isolated contact sensing is employed.

Relays with a Y type wide range power supply have a field selectable link (J2) on the contact sensing

board to match the nominal power supply input voltage of 48 Vdc or 125 Vdc. Selection must be done at

the time of installation and prior to application of power. This option is factory set for 125 Vdc. Figure 3-2

shows the link set to the 125 Vdc position.

Table 3-1. Function of Sensing Contacts

Contacts

Designation

Function

Pilot Initiate

(Optional)

(Note

∆1)

PI

Form A contact which, when closed, initiates a pilot reclosing

(Optional) sequence. This contact is also required during the

sequence to initiate each reclose attempt. ∗

Breaker

52b

Form B auxiliary contact of the controlled breaker utilized to

determine the state of the breaker.

Reclose Initiate

(Note

∆2)

RI

Form A contact which, when closed, initiates a normal reclosing

sequence. This contact is also required during the sequence to

initiate the individual time delays and subsequent reclose output

closures. ∗

Instantaneous

Reclose Bypass

IRB

Form A contact which, when closed, cause the instantaneous

reclosure attempt to be bypassed.

Drive to Lockout

DTL

Form A contact which, when closed, instantaneously drives the

Multiple Shot Reclosing Relay into lockout.

NOTES:

∗ If the appropriate initiate contact (RI or PI) is not received within the corresponding period, the relay

is forced to the lockout state.

∆1. Input is Reset Inhibit (RES INH) if option 1 is 1.

∆2. Input is Reclose Wait (REC WAIT) if option 1 is 2. Input is Reclose Permissive (RP) if option 1 is 4.