Elgar CW-P Series
Programming
Operation Manual
4-7
4.3.7
Recall Machine Settings
This menu item, when saved (not cancelled) by the user, will recall to the present
system the system state that was saved in the dialed in memory location. Valid memory
locations are 0 to 99.
RCL
nn
System state number 99 is the factory default state. The following are the default
factory settings:
• Volts: 0.0
• Frequency: 60
• Current Limit: MAX
• Current Limit Type (Shut, Fold): FOLDBACK
• Current Limit Shutdown Time: 200 ms
• Voltage Range: LOW
• Overvoltage: MAX
• Analog Input: OFF
• Clock Signal Direction: OUT
4.3.8
Specify Relay State After Power Up Initialization
This menu item specifies whether the CW automatically closes its output relay as soon
as power up self-test succeeds. In RUN mode, the relay automatically closes, as does
any properly-specified and connected slaves.
INIT
RUN, STBY
4.3.9
Clock Direction
This menu item specifies whether the clock line is used as a zero crossing indication or
a phase-locked-loop signal source.
CLOC
OUT/IN
4.3.10 Analog Input State
This menu item specifies if an analog input signal, as applied to the M/S IN connector,
will be used as the programming source for the output voltage, adjusting it from zero to
a maximum value set by the front panel controls or through GPIB/RS-232 commands.
AINP
OFF/ON