Configuration tool method, Deassociating a range extender, Master method – Zilog ZAURCT User Manual
Page 42: Deassociating a, Range extender, See the

UM022903-0311
Reconfiguration of Masters and Starters
ZAURA
™
RF Wireless Lighting Control
Installation Guide
36
1. Turn off line power to the luminaries.
2. Place Starters in the luminaries.
3. Provide line power to the luminaries. Wait a minimum of three minutes for the starters
to resynchronize to the Master. Using the special
Toggle All
mode on the Master (see
section on page 19) can help determine when all of the starters
are synchronized to the Master.
4. Apply power to all Range Extenders, if any.
5. Depress both
Associate
buttons on the Master simultaneously for at least six seconds
until the blue LED illuminates.
6. Wait until the blue LED turns off before taking any other action with the system.
Configuration Tool Method
Using the Configuration Tool decommissions only one Starter at a time; however, it does
not reduce the number of Starters counted by the Master.
1. Plug in the Configuration tool.
2. Check that the Configuration Tool power switch is in the OFF position.
3. Place the ZAURA Starter into the Configuration Tool.
4. Place the Configuration Tool power switch in the ON position.
5. Wait four seconds. If a Master is triggered to associate while the Starter is in the
Configuration Tool, the Starter will associate to the Master.
6. Turn OFF the Configuration Tool power switch.
Deassociating a Range Extender
Should it become necessary to change the type or association of a Range Extender, the
Range Extender can be recommissioned by first deassociating it, then reassociating it as
required. Two methods exist to deassociate a Range Extender, the Master Method and the
Range Extender Method.
Master Method
The Master method deassociates all powered Starters and Range Extenders associated to
the Master. It is important to first provide power to all associated devices.
1. Ensure that all associated Range Extenders are powered on.
2. Depress both
Associate
buttons on the Master simultaneously for at least six seconds
until the blue LED illuminates.
3. Wait until the blue LED turns off before taking any other action with the system.