Ctmxxx dig fwd rev – Crompton Controls M20 User Manual
Page 40

Emotron AB 01-2551-01r4
Advanced Features
39
For more information contact your local sales outlet or visit us at:
www.emotron.com
Fig. 15 Example of connection with a forward and reversing motor starter (contac-
tor).
NOTE: In order to accomplish the above result, it will be necessary for a
forward and reversing motor starter to be installed. See Fig. 15 Example of
connection with a forward and reversing motor starter (contactor).
NOTE: In Fig. 15, R1 and R2 (K1 and K2) must not be energized/on at the
same time as this will generate a short circuit. Therefore it is important
that window 65 = 2 before the relays are connected to the contactors.
S1
S2
L2
L3
L1
C
R2
R1
A-
A+
M20
L3
L2
L1
}
5
8
7
6
2
1
13
11
9
4
3
K1
U
V
W
M
K2
K1
K2
Reset
CTMxxx
DIG
FWD
REV
Alarm/Stop
20 mA
(Blocking)
Max 240 VAC (alt. 0 VDC-)
N (alt. 48 VDC+)
Window
Function
Range
35
Reverse time
3-90 s
36
Start attempts
0-5
65
Relay function
2=reverse