beautypg.com

5 setting the start delay (window 31), Setting the start delay (window 31), Programming – Crompton Controls M20 User Manual

Page 28

background image

Emotron AB 01-2551-01r4

Programming

27

8.5

Setting the Start Delay (window 31)

To avoid false alarms during start up a Start Delay must be set to allow the
motor and machine to speed up and to allow the power in-rush currents.

Programming

1. Determine in seconds how long it takes for the motor and machine to reach

speed and for the power in-rush to pass. This will be the Start Delay.

2. Go to window 31 (default = 2.0 s).

3. Press

or

to set the determined Start Delay time in seconds.

4. Press

to confirm the change.

If the monitor is being used on a self-priming pump, it may also be necessary to
set the Start Delay long enough to allow the pump to become fully primed.

Fig. 8

Start Delay.

ENTER

2.0

31

S

Example: Start Delay 2.0 s

Start Delay [31]

t

P