Emotron AB 01-2551-01r4

Programming

25

8.3

Setting number of phases (window 43)

The number of phases must be set according to the number of motor phases.
Default is 3 phases, see also chapter 5, Wiring.

8.3.1

Programming

1. Go to window 43 (default = 3PH).

2. Press

or

to set the number of phases to 1 if a single-phase motor is

used.

3. Press

to confirm the change.

8.4

Monitor function (window 05)

If separate output relays are required for overload and underload alarms, please
refer to chapter 9 and chapter 12.

Monitor

(Protection)

Indication in

window 05

Alarm

Output Relay

(default)

OVER- and UNDER-
LOAD (default)

MAX Main Alarm

Relay 1 (NC): 6-7

MAX Pre-Alarm

Relay 2 (NO): 6-8

MIN Pre-Alarm

Relay 2 (NO): 6-8

MIN Main Alarm

Relay 1 (NC): 6-7

OVERLOAD

MAX Main Alarm

Relay 1 (NC): 6-7

MAX Pre-Alarm

Relay 2 (NO): 6-8

UNDERLOAD

MIN Pre-Alarm

Relay 2 (NO): 6-8

MIN Main Alarm

Relay 1 (NC): 6-7

3PH

43

ENTER

1PH

43