Setting margins (windows 21-24)

The margins for the Auto set can be changed manually. After the adjustment,
the Auto set action must be performed again.

Setting hysteresis (window 33)

The hysteresis of an alarm level prevents the alarm relay “chattering” if the load
fluctuates even in a normal “stable” condition. This also applies to a pre-alarm.
This feature is normally only used if the main alarm latch (window 61) is set to
Off. Default = 0%.

Fig. 10 Hysteresis

Protection (Monitor function

window 05)

Window

Default

OVER- and UNDERLOAD
(Default)

21: MAX Main Alarm margin

16%

22: MAX Pre-Alarm margin

8%

23: MIN Pre-Alarm margin

8%

24: MIN Main Alarm margin

16%

OVERLOAD

21: MAX Main Alarm margin

16%

22: MAX Pre-Alarm margin

8%

UNDERLOAD

23: MIN Pre-Alarm margin

8%

24: MIN Main Alarm margin

16%

MAX Main Alarm level [11]

MIN Main Alarm level [14]

Relay 1 MAIN Alarm

Hysteresis [33]

P/%

t/s