background image

Emotron AB 01-2551-01r4

Getting Started

9

4.4

Manual setting of alarm levels,
alternative A

Running and setting at normal load

Start the motor/machine or pump and let it run at normal load, until the
Start Delay (window 31) has expired.

Read off the load on the monitor display, e.g. 65%, window 01
(or kW/HP).

Set the max. main alarm level to something between e.g. 70-85% in window
11. This must be set to the actual application requirements, maximum load
for machine/process.

Set the min. main alarm level to something between e.g. 60-45% in window
14. This must also be set to the actual application requirements.

See also Fig. 7 in section 8.4, Over- and underload monitor.