Programming

Emotron AB 01-2551-01r4

Overload and underload Monitor

Fig. 7

Overload and underload monitor.

Programming

1. Go to window 05. The default selection is Overload and Underload

monitor.

2. Press

or

to select underload or overload monitor.

3. Press

to confirm the change.

P/%

t/s

START

UNDERLOAD

OVERLOAD

OPERATION AREA

MAX Main alarm

[11]

MAX Pre-alarm

[12]

Auto set level

Normal load

MIN Pre-alarm

[13]

MIN Main alarm
[14]

Relay 1

Main alarm

Relay 2
Pre-alarm

Start delay [31]

Response

[34] [32]

MAX Pre-alarm

margin [22]

MIN Pre-alarm
margin [23]

MAX Main

alarm margin
[21]

MIN Main

alarm margin
[24]

Main Alarm latch=ON [61]

delay

05

_

_

05

_

05

_

OVER- and UNDERLOAD

UNDERLOAD

OVERLOAD

ENTER