Programming
Emotron AB 01-2551-01r4
8.2
Setting rated motor power and current
(window 41 and 42)
The rated motor power and the rated motor current must be set in windows 41
and 42.
Example motor plate:
8.2.1
Programming
1. Go to window 41 (default = 2.2 kW).
2. Press
or
to set the rated motor power as indicated on the motor
plate (see example).
3. Press
to confirm the change.
4. Go to window 42 (default = 5.6 A).
5. Press
or
to set the rated motor current as indicated on the motor
plate (see example).
6. Press
to confirm the change.
TYPE:
T56BN/4
NR:
948287
Prot. IP:
54
Serv:
S1
Cos
ϕ:
0.78
Is. Cl:
F
V:Y/
Δ
Hz
HP
kW
RPM
A:Y/
Δ
240/415
50
3
2.2
1400
5.6/9.4
260/440
60
3
2.2
1680
5.8/9.1
ASYNCHRONOUS THREE-PHASE MOTORS