CIRCUTOR CVM-NRG96 Series (Available until stocks) User Manual

Page 37

background image

CVM-NRG96

M9817250120-03-05A

37

3. The CVM-NRG96 analyzer does not correctly display the current reading. It

shows values varying between 0 to 5 amps of current.

Ensure that the Transformer Primary ratio has been correctly set; once
correctly set the current measurement shall be shown correctly extrapolated to
primary (see section on transformer ratios).

4. The CVM-NRG96 analyzer is measuring in average voltage and is displaying

the secondary voltage (for example 110 volts).

Ensure that the Primary and Secondary voltage ratio has been correctly set
(see section on transformer ratios).

5. The CVM-NRG96 analyzer does not respond to communications requests; it

does not communicate.

Ensure that the equipment's communication parameters have been correctly
set as well as the peripheral number (0 to FF).

6. The CVM-NRG96 analyzer is connected to the Power Studio System and it

does not communicate with the PC.

Ensure that the analyzer has been set with a Bus speed of 19,200 bauds.