23
Once the energy code has been selected and entered using the
key the
watts per pulse must be entered or as a default kilowatts per pulse.
{Ion
{Jofm
{l[n_
**(***
Example:
***(/**
500 watts·h/pulse
**+(/**
1.5 kilowatts·h/pulse
To write or change the watts. hour/pulse, the MAX key has to be repeatedly
pressed, increasing the value of the digit flashing at the time.
When the required value is on the screen, move on to the following digit by
pressing MIN, to allow the remaining values to be changed.
When the last digit has been changed, press MIN to move back to the first
digit, allowing the previously set values to be changed again.
Once the required option is selected, press the
key to enter the data and
so finish the equipment configuration.
Setting alarm condition
Alarm code table per condition:
Magnitude
Phase
Symbol L1
Code
Simple Voltage
L1
V 1
01
Current
L1
A 1
02
Active Power
L1
kW 1
03
Reactive Power L/C
L1
KvarL/C 1
04
Power Factor
L1
PF 1
05
% THD V
L1
THD V1
25
% THD A
L1
THD A1
28
Simple Voltage
L2
V 2
06
Current
L2
A 2
07
Active Power
L2
kW 2
08
Reactive Power L/C
L2
KvarL/C 2
09
Power Factor
L2
PF 2
10
% THD V
L2
THD V2
26
% THD A
L2
THD A2
29