beautypg.com

Spectrum Controls 1746sc-INO4vi User Manual

Page 36

background image

26

SLC 500

Isolated Analog Output Modules

Table 11. Channel status word details, Input Words 4 through 7 (I:e.4 through I:e.7)

These bit settings in the status word

Indicate this

Bit: 15 14 13 12

11 10

9

8

7

6

5

4

3

2

1

0

0

Output channel disabled

1

Output channel enabled

0

0

1

1–5 Vdc output range

0

1

0

0–5 Vdc output range

0

1

1

0–10 Vdc output range

1

0

0

0–20 mA output range

1

0

1

4–20 mA output range

1

1

0

0–21 mA output range

0

0

0

Engineering units

0

0

1

Scaled for PID

0

1

0

Proportional counts

0

1

1

1746-NO4 format

1

1

0

User-defined scale

0

Reset output on fault

1

Hold last value on fault

0

No output data limiting

1

Output data limiting

0

No error

1

Operating temperature error

0

No error

1

Over-limit error

0

No error

1

Under-limit error

0

No error

1

Over-range error

0

No error

1

Under-range error

0

No error

1

Non-fatal channel error

0

No error

1

Fatal channel error