beautypg.com

Controlling each output channel’s signal – Spectrum Controls 1746sc-INO4vi User Manual

Page 34

background image

24

SLC 500

Isolated Analog Output Modules

Figure 5. Example relationship between output signal and
channel data

Data Value

9999

100

20.5 mA

3.5 mA

Signal

Value

In the preceding example...

S

low

= 3.5

U

low

= 100

S

high

= 20.5

U

high

= 9999

S = 17

U = 9899

Controlling Each Output
Channel’s Signal

Output words 0 through 3 determine the output signal levels for channels
0 through 3, respectively. The output signal level depends on the output
range and data format selected.

Channel 0 Output Data Word

15

0

O:e.0

Address

Channel 1 Output Data Word

O:e.1

Channel 2 Output Data Word

O:e.2

Channel 3 Output Data Word

O:e.3