Spectrum Controls 1746sc-INO4vi User Manual
Page 26
![background image](/manuals/742149/26/background.png)
16
SLC 500
™
Isolated Analog Output Modules
No special I/O configuration (SPIO CONFIG) information is required.
The module ID code automatically assigns the correct number of input
and output words for the processor to access.
Figure 4. Output and input words
Channel 0 Output Data Word
15
0
O:e.0
Address
Channel 1 Output Data Word
O:e.1
Channel 2 Output Data Word
O:e.2
Channel 3 Output Data Word
O:e.3
Channel 1 Configuration Byte
Channel 0 Configuration Byte
O:e.4
Channel 3 Configuration Byte
Channel 2 Configuration Byte
O:e.5
Low Value of Output Data Limit (or User-Defined Scale)
O:e.6
High Value of Output Data Limit (or User-Defined Scale)
O:e.7
Channel 0 Data Word
15
0
I:e.0
Address
Channel 1 Data Word
I:e.1
Channel 2 Data Word
I:e.2
Channel 3 Data Word
I:e.3
Channel 0 Status Word
I:e.4
Channel 1 Status Word
I:e.5
Channel 2 Status Word
I:e.6
Channel 3 Status Word
I:e.7
Example – If you want to reconfigure channel 2 on your module, and it
is in slot 4 of the SLC chassis, you would modify the configuration word
at address O:4.5. Alternatively, if you want to obtain the status of channel
2, you would check the status word at address I:4.6.