beautypg.com

Spectrum Controls 1746sc-INO4vi User Manual

Page 30

background image

20

SLC 500

Isolated Analog Output Modules

Table 10. Data format definitions

Selected

Data Value (counts)

Corresponding Signal

Data Format

Output Range

Min.

Max.

Min.

Max.

Engineering Units

±

10 V

-10250

+10250

-10.25 V

+10.25 V

0–10 V

-500

+10250

-0.50 V

+10.25 V

0–5 V

-500

+5500

-0.50 V

+5.50 V

1–5 V

+500

+5500

+0.50 V

+5.50 V

0–20 mA

0

+20500

0.0 mA

+20.5 mA

0–21 mA

0

+21500

0.0 mA

+21.5 mA

4–20 mA

+3500

+20500

+3.5 mA

+20.5 mA

Scaled for PID

±

10 V

0

+16383

-10 V

+10 V

0–10 V

0

+16383

0 V

+10 V

0–5 V

0

+16383

0 V

+5 V

1–5 V

0

+16383

+1 V

+5 V

0–20 mA

0

+16383

0 mA

+20 mA

0–21 mA

0

+16383

0 mA

+21 mA

4–20 mA

0

+16383

+4 mA

+20 mA

Proportional Counts

±

10 V

-32768

+32767

-10.25 V

+10.25 V

0–10 V

-32768

+32767

-0.50 V

+10.25 V

0–5 V

-32768

+32767

-0.50 V

+5.50 V

1–5 V

-32768

+32767

+0.50 V

+5.50 V

0–20 mA

-32768

+32767

0.0 mA

+20.5 mA

0–21 mA

-32768

+32767

0.0 mA

+21.5 mA

4–20 mA

-32768

+32767

+3.5 mA

+20.5 mA

1746-NO4-

±

10 V

-32768

+32767

-10 V

+10 V

Compatible

0–10 V

0

+32767

0 V

+10 V

0–5 V

0

+16384

0 V

+5 V

1–5 V

+3277

+16384

+1 V

+5 V

0–20 mA

0

+31208

0 mA

+20 mA

0–21 mA

0

+32767

0 mA

+21 mA

4–20 mA

+6242

+31208

+4 mA

+20 mA

User-Defined

±

10 V

-10.25 V

+10.25 V

Scale

0–10 V

-0.50 V

+10.25 V

0–5 V

-0.50 V

+5.50 V

1–5 V

See note

+0.50 V

+5.50 V

0–20 mA

0.0 mA

+20.5 mA

0–21 mA

0.0 mA

+21.5 mA

4–20 mA

+3.5 mA

+20.5 mA

Provides direct compatibility with the 1746-NO4 module.

For the user-defined scale, the data in output words 6 and 7 determine the count limits.

See the next subsection,

Optional: Setting The Output Data Limits (or User-Defined Scale),

for information on the User-Defined Scale data format.