Spectrum Controls 1746sc-INO4vi User Manual
Page 30

20
SLC 500
™
Isolated Analog Output Modules
Table 10. Data format definitions
Selected
Data Value (counts)
Corresponding Signal
Data Format
Output Range
Min.
Max.
Min.
Max.
Engineering Units
±
10 V
-10250
+10250
-10.25 V
+10.25 V
0–10 V
-500
+10250
-0.50 V
+10.25 V
0–5 V
-500
+5500
-0.50 V
+5.50 V
1–5 V
+500
+5500
+0.50 V
+5.50 V
0–20 mA
0
+20500
0.0 mA
+20.5 mA
0–21 mA
0
+21500
0.0 mA
+21.5 mA
4–20 mA
+3500
+20500
+3.5 mA
+20.5 mA
Scaled for PID
±
10 V
0
+16383
-10 V
+10 V
0–10 V
0
+16383
0 V
+10 V
0–5 V
0
+16383
0 V
+5 V
1–5 V
0
+16383
+1 V
+5 V
0–20 mA
0
+16383
0 mA
+20 mA
0–21 mA
0
+16383
0 mA
+21 mA
4–20 mA
0
+16383
+4 mA
+20 mA
Proportional Counts
±
10 V
-32768
+32767
-10.25 V
+10.25 V
0–10 V
-32768
+32767
-0.50 V
+10.25 V
0–5 V
-32768
+32767
-0.50 V
+5.50 V
1–5 V
-32768
+32767
+0.50 V
+5.50 V
0–20 mA
-32768
+32767
0.0 mA
+20.5 mA
0–21 mA
-32768
+32767
0.0 mA
+21.5 mA
4–20 mA
-32768
+32767
+3.5 mA
+20.5 mA
1746-NO4-
±
10 V
-32768
+32767
-10 V
+10 V
Compatible
①
0–10 V
0
+32767
0 V
+10 V
0–5 V
0
+16384
0 V
+5 V
1–5 V
+3277
+16384
+1 V
+5 V
0–20 mA
0
+31208
0 mA
+20 mA
0–21 mA
0
+32767
0 mA
+21 mA
4–20 mA
+6242
+31208
+4 mA
+20 mA
User-Defined
±
10 V
-10.25 V
+10.25 V
Scale
0–10 V
-0.50 V
+10.25 V
0–5 V
-0.50 V
+5.50 V
1–5 V
See note
➁
+0.50 V
+5.50 V
0–20 mA
0.0 mA
+20.5 mA
0–21 mA
0.0 mA
+21.5 mA
4–20 mA
+3.5 mA
+20.5 mA
①
Provides direct compatibility with the 1746-NO4 module.
➁
For the user-defined scale, the data in output words 6 and 7 determine the count limits.
See the next subsection,
Optional: Setting The Output Data Limits (or User-Defined Scale),