Configuring Each
Output Channel

After installing your module, you must configure each channel by setting
bit values in each configuration word. Output words 4 and 5 of the output
image file (addresses O:e.4 and O:e.5) configure channels 0–1 and 2–3,
respectively.

Channel 1 Configuration Byte

Channel 0 Configuration Byte

15

0

O:e.4

Address

Channel 3 Configuration Byte

Channel 2 Configuration Byte

O:e.5

A detailed explanation appears in the following table:

Table 9. Channel configuration word details, Output Words 4 and 5 (O:e.4 and O:e.5)

To select…

Use these bit settings...

For Channel 1 (and 3)

For Channel 0 (and 2)

Bit: 15 14 13 12

11 10

9

8

7

6

5

4

3

2

1

0

Output channel disable

0

0

Output channel enable

1

1

±

10 Vdc output range (-INO4vi only)

0

0

0

0

0

0

1–5 Vdc output range (-INO4vi only)

0

0

1

0

0

1

0–5 Vdc output range (-INO4vi only)

0

1

0

0

1

0

0–10 Vdc output range (-INO4vi only)

0

1

1

0

1

1

0–20 mA output range

1

0

0

1

0

0

4–20 mA output range

1

0

1

1

0

1

0–21 mA output range

1

1

0

1

1

0

Invalid

1

1

1

1

1

1

Engineering units

0

0

0

0

0

0

Scaled for PID

0

0

1

0

0

1

Proportional counts

0

1

0

0

1

0

1746-NO4 compatible format

0

1

1

0

1

1

User-defined scale

1

1

0

1

1

0

Invalid

1

0

0

1

0

0

Invalid

1

0

1

1

0

1

Invalid

1

1

1

1

1

1

Reset output on fault

0

0

Hold last value on fault

1

1