Horizontal Mounting
When tightened securely, the sensor
cavity must be positioned vertically for
optimum drainage when process liquid
level drops below the sensor cavity.

An alignment mark X stamped on a
wrench flat (or on the dry face of a
flange below the housing) shows
sensor cavity orientation.

Optimum drainage occurs when the X
mark is located at 6 or 12 o’clock.

Level is detected when the sensor
cavity is filled with process liquid.

The sensor must project through a tank
fitting so that the sensor cavity is at least
1” beyond the inner wall of the tank.

Sensor Cavity

1 inch
minimum

Top View

Alignment mark

X on wrench flat

at 12 o’clock

Housing

Hub

Alternate position
for alignment
mark X: 6 o’clock

Open Sump or Basin
Do not suspend the unit by rigid
conduit installed in the electrical hub.
When installing the unit over an open
sump or basin use a suitable bracket
to support the instrument.

NOTE: The instrument must be
positioned so that overfl ow does
not fl ood the electrical housing.

Bracket