SOR Single Point RF Level Switch User Manual
Page 10
10/16
Form 759 (03.13) SOR Inc.
Instructions for EMC
651K9
When subjected to an RF Interference, the
651K9 will maintain the +1% accuracy in
all frequency ranges. In order to achieve
the stated accuracy for the 651K9, a
shielded cable, cable gland, shield bead
and the probe should be mounted in a
metallic vessel. SOR recommends using
a shielded cable made of PVC
Insulation around a tinned copper braid
shield (Olflex CY cable or equivalent).
Refer to illustrations for installation of
shield bead onto the probe wire.
Short/Fat Bead
Certificate Number: IECEx BAS 05.0054X, Issue 2
Standards: IEC 60079-0:2011, Ed 6 and IEC 60079-11:2011, Ed 6
Listing: Ex ib IIB Tx Gb (-40°C < Ta < +80°C)
Certificate Number: Baseefa 12ATEX0084X
Standards: IEC 60079-0:2011, Ed 6 and EN60079-11:2012
Condition of Safe Use: This apparatus may not be capable of
withstanding the insulation test required by Clause 6.4.12 of
IEC 60079-11:1999. This must be taken into account when installing the apparatus.
To order a new circuit board assembly, use the following part number: 99-414
Spare Parts
Instructions for IEC-Listed Product
Parameters:
Ui = 28V
Ii = 100mA
Pi = 0.75W
Li = 0
Ci = 0
NOTE: Replacement of circuit boards not allowed on agency listed units.