LINK Systems Omni II Automatic Setups Module User Manual
Page 61
October 16, 2008
Manual Version 1.1
6-7
Coarse/Inc Turn Count Out of Synch The incremental turn count does not match the coarse
resolver turn count. This could be caused by a bad connection or a
hardware problem on the rotary circuit board (5100-10C).
Rotary Transducer Read Failure The value read from the rotary transducer is invalid. This could
be caused by a bad connection, a bad rotary transducer, or a hardware
problem on the rotary circuit board (5100-10C).
Rotary Max Speed Exceeded The maximum number of revolutions per second has been
exceeded. It may be necessary to gear down the input shaft of the
rotary transducer
Unknown Transducer Type The automatic circuit board detection system has detected an
unexpected type of circuit board. The firmware on the main board
(5100-10) will need to be updated.