LINK Systems Omni II Automatic Setups Module User Manual
Page 55
October 16, 2008
Manual Version 1.1
6-1
Section 6 Diagnostics - Fault and Status Messages
When the press control screen reports a stop condition that indicates the auto-setup board
asserted or is asserting a stop signal, the “Auto-Sets” screen module status and the individual
sub-systems status line will give additional information.
Section 6.1
Main Module Messages
OK
General
Module
status
is
ok.
This does not mean that the individual
sub systems such as shut height control, counterbalance, and cushion
control are ok.
Bad Config Data
The
configuration
data
stored
in non-volatile ram was corrupted. The
Automatic Setup card will need to be reconfigured after pressing the
reset error key in the “Auto Sets” screen.
Press Running at Startup During the Automatic Setup module’s power-up sequence, the module
detected that the clutch is engaged (the press is running). The normal
cause for this error is momentary power loss to the Automatic Setup
module.
No Resolver Information The Automatic Setup module receives crankshaft position over the
High Speed Serial Bus. If this error is issued, the Automatic Setup
module has momentarily lost receipt of the crankshaft position. The
normal cause for this error is a bad connection of the High Speed
Serial Bus cable or that the card rack is powered down but the
Automatic Setup module is not.
Boot Info Corrupt
The Automatic Setup module has a corrupt Boot information block.
The normal cause for this error is a hardware failure.
Boot Program Corrupt
The Automatic Setup module has corrupt Boot code. The normal
cause for this error is a hardware failure.
Main Program Corrupt The Automatic Setup module has corrupt Program code. The normal
cause of this error is a hardware failure or the interruption of a
program update. If the program update process is interrupted (by loss
of power etc), the OIT will normally restart the update process when it
is powered back up.
Module in Boot Mode
The Automatic Setup module is in boot program execution mode.
This is normally the case during a main program update.
Memory Check Failed
The memory on the Automatic Setup module failed a memory check.
The normal cause for this error is a hardware failure.