INSTALLATION INSTRUCTIONS

CAUTION: Before installing, make certain the A.C. power is off and the
ISD-420-EM-A unit connector is disconnected.

1. LAmpS OpERATED

Refer to the chart below for the type of lamp to be operated in the emergency mode.If you have any questions regard-

ing specific lamps, contact Customer Service.

Illustration 1 Downlight Fixture

INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.

*The 6

″ violet leads provide the lamp selection option. The unit is shipped from the factory with the leads

disconnected and capped. When used with particular lamp types, violet leads should be connected to one anoth-
er. Refer to chart for lamp selection options.

2. mOUNTINg THE ISD-420-Em-A

When used with ceiling mounted downlight fixtures, the

ISD-420-EM-A should be mounted on the fixture above the

ceiling. The flex conduit marked “A” should be wired into the ballast/lamp compartment or to an electrical junction box

on the fixture which allows access to the ballast/lamp connections. Refer to Illustration 1 for typical mounting.

When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between

the battery pack and the lamp.

3. WIRINg

Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance
with the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.

4. INSTALLINg THE LIgHTED pUSH BUTTON TEST SWITCH (LpTS)

Cut a single gang switch box into the ceiling tile adjacent to the fixture within reach of the

ISD-420-EM-A flex.

After mounting the switch box, connect flex to the box and route all leads inside the box. The positive terminal

will be indicated by the red mark on the side of the LpTS switch. NOTE: For proper operation, use only the test

accessories provided with the unit. See Page 1 of the Instruction Manual.

5. WIRINg THE A.C. INpUT

A.

The

ISD-420-EM-A and A.C. ballast must be on the same branch circuit.

B. The

ISD-420-EM-A requires an unswitched A.C. power source of 110-277V 50/60HZ.

C. When the

ISD-420-EM-A is used with a switched fixture, the A.C. input to the ISD-420-EM-A must be connected

ahead of the fixture switch. Refer to Illustration 2 for switched and unswitched fixture wiring diagrams.

For 208V applications, consult Customer Service.

FLEX “A”

JUNCTION

BOX

CEILING

TILE

A.C. BALLAST &

LAMP SOCKET COMPARTMENT

FLEX “B”

SWITCH BOX

TEST SWITCH

CHARGE LIGHT

ISD-420-EM-A

LpTS

OPTION

LAMP TYPE

EMERGENCY

OPERATION

*VIOLET LEADS

1

2

13W - 32W Compact

42W - 57W Compact

One Lamp

One Lamp

Connected