INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the
I-26-EM-A unit connector is disconnected.
1. MOUNTING THE I-26-EM-A
When used with ceiling mounted downlight fixtures, the
I-26-EM-A should be mounted on the fixture above the
ceiling. The flex conduit marked “A” should be wired into the ballast/lamp compartment or to an electrical junction
box on the fixture which allows access to the ballast/lamp connections. Refer to Illustration 1 for typical mounting.
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between
the battery pack and the lamp.
2. MOUNTING THE TEST SWITCH AND CHARGE INDICATOR LIGHT
Cut a single gang switch box into the ceiling tile adjacent to the fixture within reach of the
I-26-EM-A flex
marked “B”. After mounting the switch box, connect flex “B” to the box and route all leads inside the box. Refer
to Illustration 1 for typical mounting. Connect the leads to the components as follows:
Red/Blk or Red lead w/connector
(+) Charge light terminal
Wht/Red lead
(–) Charge light terminal
White
Test switch
*Wht/Blk lead
Unit connector
White/Black
*Wht/Blk
lead
Unit
connector
* To prevent electrical shock and unintentional battery discharge, do not join the unit connector until the installation
is complete.
3. WIRING
A.
The
I-26-EM-A and A.C. ballast must be on the same branch circuit.
B.
The
I-26-EM-A requires an unswitched A.C. power source of either 120 or 277 volts; therefore, when used
with switched fixtures, the
I-26-EM-A input must be wired ahead of the switch.
C. Refer to the wiring diagrams on the back page for the proper wiring.
Illustration 1
Downlight Fixture
INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.
FLEX “A”
JUNCTION
BOX
CEILING
TILE
A.C. BALLAST &
LAMP SOCKET COMPARTMENT
FLEX “B”
SWITCH BOX
TEST SWITCH
CHARGE LIGHT
I-26-EM-A