INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the I-42-EM-TM unit connector is disconnected.
4. WIRINg
A.
When
the
I-42-EM-TM is installed on the same branch circuit, refer to Illustration 2, Figures A and B for
input wiring. When installed on separate branch circuits, refer to Illustration 2, Figures C and D for input wiring.
Per NEC, the
I-42-EM-TM and A.C. ballast must be on the same panel board.
B. The
I-42-EM-TM requires an unswitched A.C. power source of either 120 or 277 volts; therefore, when
used with switched fixtures, the
I-42-EM-TM input must be wired ahead of the switch. Refer to Illustration 2
for switched and unswitched fixture wiring diagrams.
C. Refer to the wiring diagrams on the back page for the proper wiring. For wiring diagrams of ballasts not shown,
consult our Customer Service.
5. LABELS
Attach the appropriate labels adjacent to the
TBTS. Annotate Re-lamping label for lamp type and wattage. The
Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone attempting to ser-
vice the fixture.
6. COMPLETINg INSTALLATION
When the installation is complete, switch the A.C. power on and join the
I-42-EM-TM unit connector.
Illustration 1 - Lamp Fixture
INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.
1. LAMPS OPERATED
Refer to the chart below for the type of lamp(s) operated and
the number of lamps to be operated in the emergency mode.
If you have any questions regarding specific lamps, con-
tact Customer Service.
The
6
″ violet leads provide the lamp selection option.
The unit is shipped from the factory with the leads
disconnected and capped. When used with particular
lamp types, violet leads should be connected to one
another. Refer to chart for lamp selection options.
I-42-EM-TM
EMERGENCY
LAMP
LPTS
JUNCTION
BOX
N
O
I
T
P
O
P
M
A
L
E
P
y
T
y
C
N
E
g
R
E
M
E
N
O
I
T
A
R
E
P
O
T
E
L
O
I
V
S
D
A
E
L
1
2
3
4
10W-18W
26W-42W
18W
One Lamp
One Lamp
Two Lamp
Two Lamp
Compact
Compact
Compact
Compact
Connected
Disconnected
Connected
Disconnected
10W-13W
5
6
7
18W
24W
36W
Long
Compact
Long
Compact
Long
Compact
One Lamp
One Lamp
One Lamp
Connected
Disconnected
Disconnected
2. MOUNTINg ThE I-42-EM-TM
Mount
the
I-42-EM-TM to the ballast channel, junction box, or enclosed wireway so the wire leads are not ex-
posed, at least ½
″
away from the A.C. ballast(s). Refer to Illustration 1.
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between
the battery pack and the lamp.
3. INSTALLINg ThE ThREADED BODy TEST SWITCh (TBTS)
Select a convenient location on the side of the fixture so that the
TBTS can be seen after installation. Allow for
proper clearance and drill or punch a
7
/
8
″ hole (½″ knockout). Remove the nut and push the TBTS housing into the
½
″ hole. Secure the TBTS with the nut. Connect the LED wires from the unit to the TBTS (Red/Black or Red w/
tag to Red, and White/Red to White). NOTE: For proper operation, use only the test accessories provided with the
unit. See Page 1 of the Instruction Manual.
TBTS