Installation instructions, Lamps operated, Mounting the i-42-em-j – IOTA I-42-EM-J User Manual
Page 2: Mounting the threaded body test switch (tbts), Wiring, Labels, Completing installation
![background image](/manuals/738090/2/background.png)
Page 2
INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the
I-42-EM-J unit connector is disconnected.
1. LAMPS OPERATED
Refer to the chart below for the type of lamp(s) operated and the number of lamps to be operated in the emergency mode.
If you have any questions regarding specific lamps, contact Customer Service.
INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.
N
O
I
T
P
O
P
M
A
L
E
P
y
T
y
C
N
E
g
R
E
M
E
N
O
I
T
A
R
E
P
O
T
E
L
O
I
V
S
D
A
E
L
1
2
3
4
10W-18W
26W-42W
18W
One Lamp
One Lamp
Two Lamp
Two Lamp
Compact
Compact
Compact
Compact
Connected
Disconnected
Connected
Disconnected
10W-13W
5
6
7
18W
24W
36W
Long
Compact
Long
Compact
Long
Compact
One Lamp
One Lamp
One Lamp
Connected
Disconnected
Disconnected
The
6
″ violet leads provide the lamp selection option. The unit is shipped from the factory with the leads
disconnected and capped. When used with particular lamp types, violet leads should be connected to one anoth-
er. Refer to chart for lamp selection options.
2. MOuNTINg ThE I-42-EM-J
When used with ceiling mounted downlight fixtures, the
I-42-EM-J should be mounted on the fixture above the ceiling.
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between
the battery pack and the lamp.
3. MOuNTINg ThE ThREADED BODy TEST SWITCh (TBTS)
Cut a single gang switch box into the ceiling tile adjacent to the fixture within reach of the
I-42-EM-J flex. After
mounting the switch box, connect flex to the box and route all leads inside the box. Note proper polarity of
TBTS
when installing. NOTE: for proper operation, use only the test accessories provided with the unit. See Page 1 of
the Instruction Manual.
4. WIRINg
A.
When
the
I-42-EM-J is installed on the same branch circuit, refer to Illustration 1, Figures A and B for
input wiring. When installed on separate branch circuits, refer to Illustration 1, Figures C and D for input wiring.
Per NEC, the
I-42-EM-J and A.C. ballast must be on the same panel board.
B. The
I-42-EM-J requires an unswitched A.C. power source of either 120 or 277 volts; therefore, when
used with switched fixtures, the
I-42-EM-J input must be wired ahead of the switch. Refer to Illustration 1
for switched and unswitched fixture wiring diagrams.
C. Refer to the wiring diagrams on the back page for the proper wiring. For wiring diagrams of ballasts not shown,
consult our Customer Service.
5. LABELS
Attach the appropriate labels adjacent to the
TBTS. Annotate Re-lamping label for lamp type and wattage. The
Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone attempting to ser-
vice the fixture.
6. COMPLETINg INSTALLATION
When the installation is complete, switch the A.C. power on and join the
I-42-EM-J unit connector.