INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the I-160R unit connector is disconnected.
1. LAmPS OPERATED
The
I-160R can be used with most 2
′–8′ T8, 2′–4′ T5, or 4-pin compact lamps. Refer to the chart for the type of lamp(s) oper-
ated and the number of lamps to be operated in emergency mode. Contact Customer Service with questions about specific
lamps.
*The lamp selector leads each have a 3 position shorting P-nut connector. Select the proper wire combination from the chart
for the desired lamp(s) used. Cut and strip one of the selected wires (
3
/
8
″) and plug it into the P-nut of the second wire.
2. mOUNTINg ThE I-160R
Cut a 2
5
/
8
″ section from one side of the ceiling tile. Install the unit as shown in Illustration 1. Extend the flex conduit to a conve-
nient location on top of the fixture and punch a
7
/
8
″ hole. Feed the wires and flex connector through the hole in the fixture and
secure in place with the flex connector nut.
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between the battery
pack and the lamps.
CAUTION: Properly secure the I-160R in the ceiling grid to insure compliance with local, state, and federal guidelines
regarding ceiling mounted equipment.
3. WIRINg
Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s) and ballast. Install in accordance with the
National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.
OPTION
LAmP TyPE
EmERgENCy
OPERATION
*LAmP SELECTOR LEADS
Brn/Wht
Brown
Violet
32 Watt 4-ft. T8
One Lamp
59 Watt 8-ft. T8
One Lamp
95 Watt 8-ft. T12
One Lamp
70W Compact
42W Compact
One Lamp
17 Watt 2-ft. T8
Two Lamps
One Lamp
32W Compact
One Lamp
1
2
3
4
5
6
7
28W 4-ft. T5
18W Compact
26W Compact
18W Compact
54W 4-ft. T5
47W 4-ft. T5
39W 3-ft. T5
24W 2-ft. T5
95W 4-ft. T5
8
9
10
11
12
13
14
15
16
Two Lamps
Two Lamps
One Lamp
One Lamp
One Lamp
One Lamp
One Lamp
One Lamp
One Lamp
17 Watt 2-ft. T8
One Lamp
26W Compact
One Lamp
17
18
50W Long Compact
30W Long Compact
One Lamp
One Lamp
25W Long Compact
One Lamp
19
20
21
Illustration 1 CEILING GRID INSTALLATION
CHARGE
TEST
CEILING TILE
REFER TO THE WIRING
DIAGRAMS ON THE
BACK PAGE OF THE
INSTRUCTION MANUAL
FOR THE PROPER
WIRE DIAGRAM.
FLEX
TEST SWITCH
CHARGE LIGHT
WIRING HARNESS
SIDE VIEW
BOTTOM VIEW
I-160R
I-160R