beautypg.com

13 fault finding – Glow-worm EnergySaver 80 User Manual

Page 28

background image

28

221837B

Diagram 13.1

13 Fault Finding

Before detailed checking of electrical components ensure that remote controls are calling for heat.
Check that the gas supply is free of obstructions and purged of air. Check the overheat thermostat
and fluehood thermostat have not operated. Isolate the electrical supply and physically check
ALL cables, connections and the printed circuit board (PCB) fuse. Check the air tubes to air
pressure switch.

Is there 240V

between L + N

Isolate supply

Check continuity

of overheat
thermostat.

Thermostat ok ?

Is thermostat

neon on ?

Correct power
supply problem

Isolate supply

1

Is there

continuity

between

NC

and

C

on APS

Replace APS

Check continuity of

control thermostat

between 3 and 6

ok ?

Replace control

thermostat

NO

YES

YES

Check wiring

and IC PCB

'stat' plug for

defects.

Repair or

replace wiring/

PCB if

necessary

YES

YES

NO

NO

NO

Replace

overheat

thermostat

NO

YES